Brand Name : GREEFOUN
Model Number : QXU47S6
Certification : CE
Place of Origin : CHINA
MOQ : 1piece
Payment Terms : TT, L/C, Western Union
Supply Ability : 100000pieces/year
Delivery Time : within 15days
Packaging Details : Standard Export Package
Refrigerant : R22/R134a/R407C/R410A
Tube Type : U tube
Shell material : seamless/304,316Lstainless steel pipe
Cooling capacity : 18KW~4000KW
Heat exchange tube : red copper
System : Single Circuit
Water Cooling Type Evaporator
Shell and Tube Heat Exchanger for Water Chiller
Shell tube type water cooled dry evaporator is suitable for water cooled unit, water source heat pump, air
cooled pump and air cooled heat pump unit.
The product is applying for refrigerants of R22, R134a, R407C and R410A etc.
The referigerating medium is for tap water, underground water, river water and sea water or brine, water
and glycol solution, sulfate solution, etc.
For heat exchange tube, copper pipe, copper nickel alloy tube, aluminum brass tube, stainless steel tube,
etc. The shell raw material mainly are seamless steel tube, stainless steel pipe.
1, Heat exchange tube: four main tube type.
(1) ∅ within 3/8 "thread copper coil, it is mainly used for" U "type tube evaporator.
(2) ∅ within 1/2 "threaded straight copper tube, straight tube is mainly used for dry-type evaporator.
(3) ∅ 1/2 "corrugated straight stainless steel tube, straight tube is mainly used in food industry of dry
evaporator.
(4) ∅ 5/8 "inside outside screw wing efficient copper tube, it is mainly used for air precooling industry dry
evaporator.
2, shell raw material:
There are two of the major materials:
(1) # 20 seamless steel tube, mainly used for all kinds of load - more than 20 ℃ cold agent.
(2) 304/316 l stainless steel tube, it is mainly used for food and low temperature (below 25 ℃, higher than
40 ℃) of the refrigerant, 316 l can also be used for cooling load of the sulfate for industry.
3, interface:
U SHAPED TUBE DRY EVAPORATOR (SINGLE MACHINE) CAPACITY: 18KW TO 95KW
Models | QXU18S5 | QXU28S5 | QXU35S6 | QXU47S6 | QXU56S6 | QXU65S6 | QXU80S8 | QXU95S8 | ||
Rated data ti=12°C te=2°C tu=7°C Dts=5°C | Qn | KW | 18.6 | 28.2 | 35.1 | 47 | 56 | 65 | 80 | 95 |
Kcal/h(×103 ) | 16 | 24 | 30.2 | 40.4 | 48.2 | 56.7 | 68.8 | 81.7 | ||
Wn | m3 /h | 4 | 6 | 6 | 8 | 9.6 | 11.4 | 13.8 | 16.4 | |
Wm | m3 /h | 6.3 | 8 | 10 | 11.4 | 12 | 14.5 | 18 | 21 | |
Dpn | bar | 0.16 | 0.29 | 0.27 | 0.41 | 0.35 | 0.39 | 0.42 | 0.46 |
Models | QXU18S5 | QXU28S5 | QXU35S6 | QXU47S6 | QXU56S6 | QXU65S6 | QXU80S8 | QXU95S8 | |
Dimension(mm) | A | 887 | 1037 | 1275 | 1407 | 1431 | 1431 | 1631 | 1781 |
B | 140 | 140 | 168 | 168 | 168 | 168 | 219 | 219 | |
C | 97 | 97 | 107 | 107 | 161 | 161 | 161 | 161 | |
D | 690 | 840 | 1040 | 1190 | 1030 | 1180 | 1380 | 1530 | |
E | 180 | 180 | 200 | 200 | 200 | 200 | 240 | 240 | |
Vent | S1 | 1/2 | 1/2 | 1/2 | 1/2 | 1/2 | 1/2 | 1/2 | 1/2 |
Outlet | S2 | 1/2 | 1/2 | 1/2 | 1/2 | 1/2 | 1/2 | 1/2 | 1/2 |
Connection | W(DN) | 40 | 40 | 50 | 50 | 65 | 65 | 65 | 65 |
D1(mm) | 22 | 22 | 22 | 22 | 22 | 22 | 22 | 22 | |
D2(mm) | 35 | 35 | 35 | 35 | 54 | 54 | 54 | 54 | |
P(kg) | 49 | 58 | 72 | 78 | 88 | 93 | 125 | 136 | |
Qn-rated refrigerating capacity Wn-cooling water flow Wm-maximum cooling water flow Dpn-pressure drop of recirculating cooling water Dts-overheat temperature |